SPECIFICATION
Application
Supply Air in Controlled Environments
Filter Classification
H14-U16
Type
Panel filter in Fluid Seal, Knife Edge or Dry Seal
Nominal Airflow (m/s)
0.45m/s
Media
PolyTetraFluorEthylene (PTFE) 35mm or 50mm pack depth
Air Volume (m³/hr)
150-2220
Gasket
Urethane Foamed, Closed Cell Neoprene, EDPM or Urethane Gel
Initial Pressure drop (Pa)
40-65Pa @ 0.45 m/s
Separator
Thermoplastic hotmelt
Temperature (max)
70 ºC in continuous operation
Filter test
Conform EN1822 NEN-EN-ISO 29463