Back Radicel P Panel Filters

SPECIFICATION


Application
Supply Air in Controlled Environments

Filter Classification
H14-U16

Type
Panel filter in Fluid Seal, Knife Edge or Dry Seal

Nominal Airflow (m/s)
0.45m/s

Media
PolyTetraFluorEthylene (PTFE) 35mm or 50mm pack depth

Air Volume (m³/hr)
150 - 2220

Gasket
Urethane Foamed, Closed Cell Neoprene, EDPM or Urethane Gel

Initial Pressure drop (Pa)
40-65Pa @ 0.45 m/s

Separator
Thermoplastic hotmelt

Temperature (max)
70 ºC in continuous operation

Filter test
Conform EN1822 NEN-EN-ISO 29463
Conform to UL900

Frame
Extruded Aluminium

Product Enquiry